XGI
Fast, Compact, Open Network Solution IEC standard programming
- LD (Ladder Diagram), ST (Structured Text)
SFC (Sequential Function Chart)
Summary
XGT series is new-concept, new-generation industrial solution based on Open Network, High-speed processing, Compact size, Easy-to-use programming. XGT Series offers useful lineups and various network & special modules so that you can configure optimum system for your industrial purpose and system scale.
Speed Innovation...Fast
MPU (NGP 1000) developed by LSIS accomplishes the fastest CPU processing speed(0.028㎲ / step). And LSIS-dedicated bus controller and High-speed transmission algorithm achieve high performance of internal interface.
Size Innovation ... Compact
The smallest size (dimensions 27×98×90) achieves cost-efficiency and various applications.
Network Innovation ... Flexible
System integration of Open Network: XGT series support various communication solutions ranging from field control to information level with Fast Ethernet, Profibus-DP, DeviceNet, MODBUS and even MECHATROLINK-II.
Software Innovation ... Intelligent
XG5000 Software Package provides integrated engineering environment from basic programming to different special module setting as well as diagnosis. This package consists of XG5000 (Programming), XG-PD (Network) and APM Software Package (Positioning).
Software Innovation ... Intelligent
XG5000 Software Package provides integrated engineering environment from basic programming to different special module setting as well as diagnosis. This package consists of XG5000
Engineering & Programming Innovation ... Easy
XGT series expand device memory and support advanced programming environment with Index register (Z), File register (U), and Analog register (U).
XGI-CPUU (IEC Standard)
ㆍProgram capacity: 1Mbyte
ㆍI/O points: 6,144
ㆍI/O device point: 131,072 (Remote I/O)
ㆍProcessing speed: 28ns/step
ㆍIEC 61131-3 standard programming
- LD(ladder), SFC(Sequential Function Chart)
ST(Structured Text)
User defined FB (Function block)
ㆍPowerful built-in PID and Process control
- Max. 256 loops and variety of process functions
ㆍUtilize the same I/O with XGK CPU
ㆍEnable to convert from GLOFA PLC program to XGI program
XGI-CPUH (IEC Standard)
ㆍProgram capacity: 512Kbyte
ㆍI/O points: 6,144
ㆍI/O device point: 131,072 (Remote I/O)
ㆍProcessing speed: 28ns/step
ㆍIEC 61131-3 standard programming
- LD(ladder), SFC(Sequential Function Chart)
ST(Structured Text)
User defined FB (Function block)
ㆍPowerful built-in PID and Process control
- Max. 256 loops and variety of process functions
ㆍUtilize the same I/O with XGK CPU
ㆍEnable to convert from GLOFA PLC program to XGI program
Item | XGI-CPUU |
XGI-CPUH |
||
Operation system |
Reiterative operation, fixed cycle operation, constant scan |
|||
I/O Control system |
Scan synchronous batch processing system(refresh system), direct system by command |
|||
Program language |
Ladder Diagram, SFC(Sequential Function Chart), ST(Structured Text), IL(Read only) |
|||
No. of commands |
Operator |
18 |
||
Basic function |
136 types + real number operation function |
|||
Basic function blcok |
43 |
|||
Dedicated function block |
Dedicated function blocks by special function modules, communication dedicated function block(P2P) |
|||
Operation processing speed (basic command) |
Basic |
0.028 ㎲/step |
||
MOVE |
0.084 ㎲/step |
|||
Real number operator |
± : 0.392㎲(S), 0.924㎲(D) |
|||
Program memory capacity |
1Mbyte |
512Kbyte |
||
I/O points(installable) |
6,144points |
|||
Max. I/O memory contact |
131,072points |
|||
Data memory |
Symbolic variable area(A) |
512KB(max. 256KB retain settable) |
||
I variable(I) |
16Kbyte |
|||
Q variable(Q) |
16Kbyte |
|||
Direct variable |
M |
256KB (max. 128KB retain settable) |
||
R |
64Kbyte * 2block |
|||
W |
128Kbyte |
|||
Flag variable |
F |
4Kbyte |
||
K |
16Kbyte |
|||
L |
22Kbyte |
|||
U |
8Kbyte |
|||
Flash area |
2 Mbyte, 32block |
|||
Timer |
No point limit |
|||
Counter |
No point limit |
|||
Program structure |
Total no. of programs |
256 |
||
Initialization task |
1 |
|||
Fixed cycle task |
32 |
|||
Internal device task |
32 |
|||
Operation mode |
RUN, STOP, DEBUG |
|||
Restart mode |
Cold, Warm |
|||
Self diagnosis |
Operation delay monitoring, memory fault, |
|||
Built-in function |
Modbus slave, PID |
|||
Download port |
RS-232C(1CH), USB(1CH) |
|||
Data protection in case of power failure |
Retain area setting by basic parameters |
|||
Max. base extension |
8 |
|||
Current consumption(mA) |
960 |
|||
Weight (kg) |
0.12 |
|||