XGI

XGI


Product Code: XGI
Availability: In Stock
XGI in Pakistan , LG XGI in Karachi, Lsis XGI distributor

Fast, Compact, Open Network Solution IEC standard programming
- LD (Ladder Diagram), ST (Structured Text)
SFC (Sequential Function Chart)


Summary
XGT series is new-concept, new-generation industrial solution based on Open Network, High-speed processing, Compact size, Easy-to-use programming. XGT Series offers useful lineups and various network & special modules so that you can configure optimum system for your industrial purpose and system scale.



Speed Innovation...Fast
MPU (NGP 1000) developed by LSIS accomplishes the fastest CPU processing speed(0.028㎲ / step). And LSIS-dedicated bus controller and High-speed transmission algorithm achieve high performance of internal interface.
Size Innovation ... Compact
The smallest size (dimensions 27×98×90) achieves cost-efficiency and various applications.
Network Innovation ... Flexible
System integration of Open Network: XGT series support various communication solutions ranging from field control to information level with Fast Ethernet, Profibus-DP, DeviceNet, MODBUS and even MECHATROLINK-II.
Software Innovation ... Intelligent
XG5000 Software Package provides integrated engineering environment from basic programming to different special module setting as well as diagnosis. This package consists of XG5000 (Programming), XG-PD (Network) and APM Software Package (Positioning).
Software Innovation ... Intelligent
XG5000 Software Package provides integrated engineering environment from basic programming to different special module setting as well as diagnosis. This package consists of XG5000
Engineering & Programming Innovation ... Easy
XGT series expand device memory and support advanced programming environment with Index register (Z), File register (U), and Analog register (U).


XGI-CPUU (IEC Standard)

ㆍProgram capacity: 1Mbyte
ㆍI/O points: 6,144
ㆍI/O device point: 131,072 (Remote I/O)
ㆍProcessing speed: 28ns/step
ㆍIEC 61131-3 standard programming
- LD(ladder), SFC(Sequential Function Chart)
ST(Structured Text)
User defined FB (Function block)
ㆍPowerful built-in PID and Process control
- Max. 256 loops and variety of process functions
ㆍUtilize the same I/O with XGK CPU
ㆍEnable to convert from GLOFA PLC program to XGI program



XGI-CPUH (IEC Standard)

ㆍProgram capacity: 512Kbyte
ㆍI/O points: 6,144
ㆍI/O device point: 131,072 (Remote I/O)
ㆍProcessing speed: 28ns/step
ㆍIEC 61131-3 standard programming
- LD(ladder), SFC(Sequential Function Chart)
ST(Structured Text)
User defined FB (Function block)
ㆍPowerful built-in PID and Process control
- Max. 256 loops and variety of process functions
ㆍUtilize the same I/O with XGK CPU
ㆍEnable to convert from GLOFA PLC program to XGI program

 

 




Item XGI-CPUU

XGI-CPUH


Operation system

Reiterative operation, fixed cycle operation, constant scan


I/O Control system

Scan synchronous batch processing system(refresh system), direct system by command


Program language

Ladder Diagram, SFC(Sequential Function Chart), ST(Structured Text), IL(Read only)


No. of commands

Operator

18

Basic function

136 types + real number operation function

Basic function blcok

43

Dedicated function block

Dedicated function blocks by special function modules, communication dedicated function block(P2P)


Operation processing speed (basic command)

Basic

0.028 ㎲/step

MOVE

0.084 ㎲/step

Real number operator

± : 0.392㎲(S), 0.924㎲(D)
X : 0.896㎲(S), 2.240㎲(D)
÷ : 0.924㎲(S), 2.254㎲(D)


Program memory capacity

1Mbyte

512Kbyte


I/O points(installable)

6,144points


Max. I/O memory contact

131,072points


Data memory

Symbolic variable area(A)

512KB(max. 256KB retain settable)

I variable(I)

16Kbyte

Q variable(Q)

16Kbyte

Direct variable

M

256KB (max. 128KB retain settable)

R

64Kbyte * 2block

W

128Kbyte

Flag variable

F

4Kbyte

K

16Kbyte

L

22Kbyte

U

8Kbyte


Flash area

2 Mbyte, 32block


Timer

No point limit
Time range: 0.001~4,294,967.295 second
(1,193 hours)


Counter

No point limit
Coefficient range: 64 bit expression


Program structure

Total no. of programs

256

Initialization task

1

Fixed cycle task

32

Internal device task

32


Operation mode

RUN, STOP, DEBUG


Restart mode

Cold, Warm


Self diagnosis

Operation delay monitoring, memory fault,
I/O fault, battery fault, power fault and etc


Built-in function

Modbus slave, PID


Download port

RS-232C(1CH), USB(1CH)


Data protection in case of power failure

Retain area setting by basic parameters


Max. base extension

8


Current consumption(mA)

960


Weight (kg)

0.12